The SHARC Series

INDUSTRIAL FILTRATION, HEATING & COOLING USING WASTEWATER

The industrial-sized SHARC utilizes the power of wastewater for both heating & cooling for the large capacity requirements of multi-family residential, commercial & energy districts.

Why SHARC series?

  • Patented, high efficiency wastewater filtration system – pre-screening NOT required
  • Scalable to accommodate larger flow rates
  • Can be paired with all types of water-source condensers and heat pumps
  • Designed inside foundation, leaving rooftops available for greenspace & PV, extending lifespan & ease of service
  • Replaces / reduces cooling tower use, saving potable water
  • Quiet operation – no need for sound proofing or vibration mitigation

Heating / Energy recovery

Cooling / Energy rejection

Product Image of the SHARC Wastewater Heat Recovery System

Features

  • Sizes range from 6 to 12 inch piping (100 to 4500 GPM)
  • Automated reversing valves control back flush, keeping the heat exchanger operating at design parameters
  • DDC integration with touch screen control, remote monitoring, data trending, and email alerts (Modbus standard and BACnet integration available)
  • Sensors included: Temperature, pressure, flow meters
  • Expected lifespan of 25 years

Specifications

SHARC 660 SHARC 880 LF SHARC 880 SHARC 1212
Type of Process Continuous flow
Water heating YES
Wastewater cooling YES
Space heating/cooling YES
Design wastewater flowrate 100 - 550 GPM 500 - 850 GPM 750 - 1,600 GPM 1,500 - 4,500 GPM
6 - 35 L/s 31 - 54 L/s 47 - 100 L/s 95 - 280 L/s
Design condenser water flow rate Varies
Varies
Standard design heat output, at max flow 2,474 MBH 3,824 MBH 7,197 MBH 20,242 MBH
0.725 MW 1.12 MW 2.11 MW 5.93 MW
Filter size 1/8"
3 mm
SHARC module inlet/outlet connection diameter 6" 8" 8" 12"
152 mm 203 mm 203 mm 305 mm
Maximum Operating pressure 45 psi
Components included on skid Macerator unit
SHARC unit
Automated valve assembly
Heat exchanger
Control panel
Auxiliary components (supplied by others) Wastewater Holding Tank
Solids-handling wastewater supply pump(s)
Circulation pump(s)
Heat pump (optional)
DHW Pre-heat tank
Condenser Water Loop Mechanical Equipment
Condenser Water Pump VFDs
Storage/Buffer Tanks
Auxiliary Heat Injection/Rejection Equipment
SHARC 660 SHARC 880/880LF SHARC 1212
Power 208/230 V, 60 Hz, 3 Phase 460 V, 60 Hz, 3 Phase 575 V, 60 Hz, 3 Phase 208/230 V, 60 Hz, 3 Phase 460 V, 60 Hz, 3 Phase 575 V, 60 Hz, 3 Phase 208/230 V, 60 Hz, 3 Phase 460 V, 60 Hz, 3 Phase 575 V, 60 Hz, 3 Phase
Components HP KW FLA (A) FLA (A) FLA (A) HP KW FLA (A) FLA (A) FLA (A) HP KW FLA (A) FLA (A) FLA (A)
Macerator 5 3.7 13.9 6.7 5.3 5 3.7 13.9 6.7 5.3 10 7.5 25.4 12.0 9.6
Auger Motor 0.75 0.6 3.3 1.7 1.3 1.5 1.1 4.6 2.1 1.7 1.5 1.1 4.6 2.1 1.7
Solids Pump Motor 1 0.75 3.3 1.5 1.4 3 2.2 8.5 3.8 3.0 5 3.7 13.6 6.2 4.9
Controls - - 5.0 2.0 2.0 - - 5.0 2.0 2.0 - - 5.0 2.0 2.0
Nominal Load 25.5 11.9 10.0 32.0 14.6 12.0 48.6 22.3 18.2
MCA (A) 29.0 13.6 11.3 35.5 16.3 13.3 55.0 25.3 20.6
MOCP (A) 40.0 20.0 20.0 50.0 25.0 20.0 80.0 35.0 30.0
S.C.R (kA) 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0

Base Module Values Only – Does not include auxiliary equipment such as wastewater supply pump(s), sludge pump(s), load side circulation pump(s), etc. that may optionally be included in the SHARC module control package.

You’re viewing SHARC Series – switch to PIRANHA Series?